A technician measures 0.3 ohms between the grounding electrode conductor connection point and a remote PV array frame during a bonding continuity check. Which statement is most accurate?
Practise this Solar PV NABCEP question free, then download the PDF, watch the video walkthrough, or unlock timed mock exams for the full web bank.
AThe reading is acceptable; NEC does not specify a maximum resistance for equipment bonding continuity
BThe reading exceeds the 0.1-ohm NEC maximum and the bond must be re-made
CThe reading exceeds the 0.25-ohm NEC maximum and the bond must be re-made
DThe reading is unacceptable only if the system voltage exceeds 1000 V
✓ Correct answer: A. The reading is acceptable; NEC does not specify a maximum resistance for equipment bonding continuityNEC Article 250 does not impose a specific maximum ohmic value for equipment bonding continuity; the requirement is a 'permanent and effective' low-impedance path. The test verifies conductivity, and acceptance criteria come from the commissioning specification or industry practice rather than a single NEC number.